Description
Carbon Monoxide Transmitter, 0 to 200 PPM CO, 4 to 20 mA/2 to 10 VDC outputs, rectangular enclosure
Specifications
- Sensor:
- Field replaceable electrochemical, 4 year typical lifespan.
- Range:
- 0 to 200 ppm.
- Coverage Area:
- 5000 to 7000 sq. ft. typical.
- Accuracy:
- ±2% FS at the time of calibration.
- Output Drift:
- <5% per year in air.
- Temperature Limits:
- -4 to 122°F (-20 to 50°C).
- Storage Temperature:
- For best sensor life, 32 to 68°F (0 to 20°C).
- Humidity Limits:
- 15 to 90% RH constant; 0 to 99% RH intermittent.
- Response Time:
- <45 s. to 90% of final value.
- Calibration:
- 15 turn span and zero adjustment potentiometers.
- Housing:
- UV resistant polycarbonate.
- Output:
- Jumper selectable 4 to 20 mA (loop powered) or 2 to 10 V (load must be >50 KΩ).
- Power Requirements:
- Current Output: 18 to 28 VDC;
Voltage Output: 18 to 28 VDC/VAC, reverse polarity protected. - Electrical Connection:
- Removable terminal block, includes two PG11 and one PG 16 knockouts for conduit fitting.
- Weight:
- 0.28 lb (0.11 kg).
- Agency Approvals:
- CE.