Dwyer PFT-IAN-S111-S

$0.00

Insertion paddlewheel flow sensor, 4-20 mA output, 316SS body, 1-1/2″ NPT connection, FKM seals, tungsten-carbide shaft, PTFE bearing.

Description

Insertion paddlewheel flow sensor, 4-20 mA output, 316SS body, 1-1/2″ NPT connection, FKM seals, tungsten-carbide shaft, PTFE bearing

Specifications

Service:
Water-based fluids.
Range:
1.2 to 25 ft/s (0.37 to 7.62 m/s).
Wetted Materials:
Body and fitting: Brass or 316 SS; Fitting O-ring: FKM standard, silicone or Buna-N optional; Impeller: 316 SS; Shaft: tungsten carbide standard or 316 SS optional; Bearing: PTFE standard.
Linearity:
±1.0% of FS.
Repeatability:
±0.5% of FS.
Temperature Limits:
-40 to 212°F (-40 to 100°C).
Pressure Limits:
400 psig (27.6 bar) @ 100°F (37.8°C), 325 psig (22.4 bar) @ 212°F (100°C).
Process Connection:
1-1/2″ NPT male standard, 2″ NPT male optional.
Output:
> Pulse: NPN open collector with square wave output, rated 60 V @ 50 mA maximum.
Frequency: 3.2 to 200 Hz. Pulse Width: 2.5 msec ±25%.
4 to 20 mA: 4 mA is 0 ft/s, 20 mA is 25 ft/s.
Power Requirement:
10 to 35 VDC.
Power Consumption:
40 mA (max).
Electrical Connection:
22 AWG shielded UL type PTLC rated 105°C, 20′ (6.1 m) long with cable gland. Can be extended up to 2000′ (609 m) with similar cable. Optional UL listed burial rated cable.
Enclosure Rating:
NEMA 6P (IP67) *.
Housing Materials:
Brass or 316 SS.
Weight:
3 lb. (1.36 kg).
Agency Approvals:
CE.
*Brass units IP67 only.

Data Sheet

Data Sheet Dwyer PFT-IAN-S111-S PFT – Data Sheet